Functions
8.2 Inverter control
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
167
You select the command data set using parameter p0810. To do this, you must interconnect
parameter p0810 with a control command of your choice, e.g. a digital input.
Figure 8-5 Example for the various command data sets
You obtain the interconnection as in the example above, if you configured the interfaces of
the inverter with p0015 = 7 in the basic commissioning, also see Section Basic
commissioning (Page 84).
An overview of all the parameters that belong to the command data sets is provided in the
List Manual.
Note
The converter require
s approx. 4 ms to switch over the command data set.