8.9 Application-specific functions
SINAMICS G110M Operating Instructions
212 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Parameter
Description
p3320
p3329
Flow characteristic
Factory setting of the flow characteristic
To set the characteristic, you require the following data from the machine manufactur-
er for each speed interpolation point:
The flow rate of the fluid-flow machine associated with the 5 selected converter
speeds
The power drawn at constant speed associated with the five flow rates corre-
sponds to the line frequency and mechanical throttling of the flow rate.
r0039
Energy display [kWh]
[0]
Energy balance
Energy usage since the last reset
[1] Energy drawn since the last reset
[2]
Energy fed back since the last reset
p0040
Reset energy consumption display
A signal change 0 1 sets r0039[02] = 0, r0041 = 0 and r0042 = 0.
r0041
Energy consumption saved
(kWh)
Energy saved referred to 100 operating hours.
For less than 100 operating hours, the inverter interpolates the energy saving to 100
operating hours.
r0042
CO: Process energy display
[1 1 Wh]
For display as process variable. Enable with p0043.
[0]
Energy balance
Energy consumption since the last reset.
[1]
Energy drawn since the last reset
[2]
Energy fed back since the last reset.
p0043
BI: Enable energy usage display
1 signal: Process energy display is active in r0042.