EasyManua.ls Logo

Siemens SINAMICS G110M - Page 226

Siemens SINAMICS G110M
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
8.9 Application-specific functions
SINAMICS G110M Operating Instructions
226 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
7. If the load sags after switching on the motor, then you must increase the motor torque
when opening the motor holding brake. Depending on the control mode, you must set
different parameters:
U/f operation (p1300 = 0 to 3):
Increase p1310 in small steps.
Increase p1351 in small steps.
Vector control (p1300 20):
Increase p1475 in small steps.
8. Switch off the motor.
9. Check the behavior of the drive immediately after the motor has been switched off:
If the motor holding brake closes too late, the load briefly sags before the motor
holding brake closes.
Set a larger value for p1217.
If the motor waits too long before switching off after the motor holding brake has
closed, reduce p1217.
You have commissioned the "Motor holding brake" function.
Table 8- 20 Setting the control logic of the motor holding brake
Parameter
Description
p1215 = 1
Enable motor holding brake
0 Motor holding brake locked (factory setting)
1 Motor holding brake just like the sequence control
2: Motor holding brake permanently open
3: Motor holding brake just like the sequential control, connected via BICO
p1216
Motor holding brake opening time
(factory setting 0.1 s)
p1216 > braking signal relay runtimes + brake release time
p1217
Motor holding brake closing time
(factory setting 0.1 s)
p1217 > braking signal relay runtimes + brake closing time
r0052.12
"Open motor holding brake" command
Table 8- 21 Advanced settings
Parameter
Description
p0346
Magnetizing time
(factory setting 0 s)
During this time the induction motor is magnetized. The inverter calculates this pa-
rameter using p0340 = 1 or 3.
p0855
Open motor holding brake (imperative) (factory setting 0)
p0858
Close motor holding brake (imperative) (factory setting 0)
p1226
Stationary state detection speed threshold
(factory setting 20 rpm)
When braking with OFF1 or OFF3, when the speed falls below this threshold, stand-
still is detected and the monitoring time p1227 or p1228 is started
p1227
Stationary state detection monitoring time (factory setting 300 s)
p1228
Pulse deletion delay time (factory setting 0.01 s)

Table of Contents

Other manuals for Siemens SINAMICS G110M

Related product manuals