Appendix
A.6 Interconnecting signals in the inverter
SINAMICS G110M Operating Instructions
324 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Explanation of the example using the ON/OFF1 command
Parameter p0840[0] is the input of the "ON/OFF1" block of the inverter. Parameter r20031 is
the output of the AND block. To interconnect ON/OFF1 with the output of the AND block, set
p0840 = 20031.
Figure A-6 Interconnecting blocks by setting p0840[0] = 20031
Principle for interconnecting blocks
Always interconnect the input (connector or binector input) with the signal source.
Note
For the basic commissioning, you determine the function of the interfaces for your converter
via predefined settings (p0015).
If you subsequently select a different predefined setting for the function of the interfaces,
then all interconnections that you c
hanged will be lost.