EasyManua.ls Logo

Siemens SINAMICS G110M - Page 58

Siemens SINAMICS G110M
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
4.3 Electrical Installation
SINAMICS G110M Operating Instructions
58 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Power Module (PM), in this case, the standby current of the Converter increases, by an
additional current of 15 mA.
The standby currents for all the possible combinations of the SINAMICS G110M are given in
the following table:
Table 4- 3 SINAMICS G110M Standby currents
Device
Power supply
Standby current (mA)
G110M FSA (0.37 ... 1.5 kW)
Mains only
325
G110M FSB (2.2 ... 4.0 kW) Mains only 445
G110 FSA + Optional 24 V PSU
or External 24 V
Mains + Optional 24 V PSU or
External 24 V*
340
G110 FSB + Optional 24 V PSU
or External 24 V
Mains + Optional 24 V PSU or
External 24 V*
460
PROFIBUS / USS CM only External 24 V only* (mains sup-
ply switched off)
235
PROFINET / AS-i CM only External 24 V only* (mains sup-
ply switched off)
290
* The optional 24 V PSU is an orderable item which is designed specifically for use with the
SINAMICS G110M converter. The 24 V PSU is fitted to the terminal housing as shown in Installing
the 24V power supply (Page 54). The external 24 V supply is sourced by the user and is connected
to the converter through the 24 V connections as shown in Connection and cables (Page 63).
The maximum combined current for all digital inputs is 200 mA, the maximum combined currents for
all the digital outputs is 500 mA.

Table of Contents

Other manuals for Siemens SINAMICS G110M

Related product manuals