3. To enable Time Average entry press <Right Arrow>.
4. Use the numeric keys to type the new Time Average setting.
5. To register the new value press <ENT>.
Setting SmartSlew :
1. From the [Dual Path Flow] menu scroll to the [Operation Adjust] menu and press <Right
Arrow>.
2.
At the [Damping Control] menu press the <Right Arrow> and move the cursor down to
[SmartSlew].
3. To access SmartSlew option list press <Right Arrow>.
4. Scroll the numeric list to the desired choice by pressing <Up/Down Arrow>.
5. To register the new value press <ENT>.
Deadband Control
Use the Deadband Control to instruct the flowmeter to report zero flow if the flow rate falls
below a specified level (usually a very low rate). It will prevent the possibility of data scatter (a
natural result of digital computation) from causing false Totalizer accumulation during long non-
flowing periods. Inspect the actual data scatter during zero flow conditions to find the proper
Deadband setting for your application.
To edit Deadband default setting (0.000):
1. From the [Dual Path Flow] menu scroll to the [Operation Adjust] menu and press <Right
Arrow>.
2. Scroll to the [Deadband Control] menu
3. Press <Right Arrow>to enable numeric entry.
4. Use the numeric keys to type in the desired rate (using selected flow rate units).
5. To register the new value press <ENT>.
Functions
7.4 Operation Adjust Menu Settings
FUP1010 IP67 Portable Flowmeter
82
Operating Instructions, 02/2010, A5E02951522A Revision 01