Installation / Preparation for Commissioning
TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany
Page 20 of 154 TR - ECE - BA - GB - 0139 - 02 11/21/2019
3.4 PROFIsafe destination address F_Dest_Add
The measuring system may be destroyed or damaged or its function be
impaired by penetration of foreign bodies and ingress of moisture!
Firmly close the access to the address switches with the screw plug
after the settings have been made.
Use the PROFIsafe destination address for the address assignment of the F-parameter F_Dest_Add.
Valid addresses: 1…65534, see also Chapter “F_Source_Add / F_Dest_Add“ on Page 135.
The PROFIsafe destination address is set via two HEX rotary switches. See pin assignment for
location and switch assignment.