Parameterization and configuration
TR-Electronic GmbH 2019, All Rights Reserved Printed in the Federal Republic of Germany
Page 82 of 154 TR - ECE - BA - GB - 0139 - 02 11/21/2019
6.3.4 Configurable submodule-related F-parameters (F_Par)
The safety-related parameters are defined with the F-Parameters of the safety-related submodules
Telegram 36 (BP/XP) and Telegram 37 (BP/XP). The secure transmission of F-Parameters
requires a CRC calculation, see Chapter 6.3.2 on Page 76.
The F-Parameter can be set according to the following table via an input box in the configuration tool
and are automatically sent by the control to the measuring system during start-up via the record data
object with index 0x0002.
Malfunctions which are caused by improper parameterization result in the
danger of death, serious physical injury and/or damage to property!
The system manufacturer must ensure proper functioning by carrying
out a protected test run during commissioning and whenever
parameters have been changed.
1: uses F_iPar_CRC: requires F_iPar_CRC
1: Source address = 1
Range: 1-65534
1: Destination address = 1
Range: 1-255
125 ms: Watchdog time = 125
Range: 10-10000 ms
12275: CRC of F-parameters = 12275
Range: 0-65535
33393: CRC of F-parameters = 33393
Range: 0-65535
1132081116: CRC iParameter = 1132081116
Range: 0-4294967295
________________________________
X: applicable
–: not applicable
Centralized and detailed description of the F-parameters,
see Chapter 6.8 from Page 135.