6.2.3 Configurable module-related parameters
The parameters of the modules Channel 1 (PNO) and Channel 2 (PNO) can be set according
to the following table via an input box in the configuration tool and are automatically sent by the control
to the measuring system during start-up via the record data object with index 0xBF00.
Parameter
initialization
(PNU 65005_0-1)
Parameter initialization controller
0: PRM Data Block
1: RAM Data
Class 3 and 4
Parameter Write
protection
(PNU 65005_2-4)
Parameter access control
0: Write all
1: Read-only
Class 3 and 4
Write protection
(PNU 65005_5)
Parameter Control
(PNU 65005) +
Save parameter
(PNU 971)
Access control to parameters PNU
65005 and PNU 971
0: Write all
1: Read-only
Class 3 and 4
Write protection
(PNU 65005_6) for
Parameter Reset
(PNU 972)
Access control to parameters
PNU 972
0: Write all
1: Read-only
Class 3 and 4
Counting direction
0: CW
1: CCW
Class 4
Encoder Class 4
functionality
Enable Class 4 functionality
0: disable
1: enable
Class 4
Preset affects for signal G1_XIST1
0: enable
1: disable
Class 4
Enable scaling
0: disable
1: enable
Class 4
Enable via alarm channel control
0: disable
1: enable
(only in compatibility mode)
Compatibility with Encoder Profile
V3.1
0: enable
1: disable
Class 3 and 4
Continued on next page