iSTAR eX Diagnostic Tests
7–6 iSTAR eX Installation and Configuration Guide
displays on the LED for approximately one second. However, since outputs
activate faster than the one-second LCD display, the LCD does not display all
output information.
To activate the output change display test, set rotary switch SW1 to the
position shown in Table 7.4.
Output Test Mode
The output test mode activates all outputs, one by one. Test results are
indicated by the LED associated with each output.
To activate the output test, set switch SW1 to the position shown in Table 7.5.
Input Change Display Mode
The input change display mode tests and displays information about inputs
that are activated manually. Inputs tested can be attached to iSTAR eX
through the CGM, readers, and I/8 boards.
Information displays on the LED for either one second (Position 4, On) or two
seconds (Position 3, On).
To activate input change display tests, set the SW1 rotary switch to the
positions shown in Table 7.6.
Table 7.4: Output Change Display Settings
Switch
Position Function
SW1-6 Activate output change display test for one second, all outputs.
(Fast mode)
Table 7.5: Output Test Switch Settings
Switch
Position Function
SW1-7 Output Test Mode activates and tests all onboard outputs one by
one.