Table 3-6 shows power requirements for Software House readers.
Table 3-6: Software House Reader Power Requirements
Reader Model Numbers Current Draw at 12 VDC
RM with Multi-Technology Reader RM1-4000, RM2-4000 300 mA max
RM with Multi-Technology Reader and LCD RM2L-4000 300 mA max
RM with mag stripe RM1-MP, RM2-MP 80 mA max
RM with mag stripe and LCD RM2L-MP 180 mA max
RM with mag stripe mullion RM3-MP 80 mA max
RM with Indala proximity RM1-P, RM2-PI 80 mA max
RM with Indala proximity and LCD RM2L-PI 180 mA max
RM with HID proximity RM1-PH, RM2-PH 250 mA max
RM with HID proximity and LCD RM2L-PH 250 mA max
RM with HID proximity mullion RM3-PH 250 mA max
RM with Wiegand RM1-W 80 mA max
Multi-Technology Contactless Reader SWH-4000
a
, SWH-4100
a
SWH-4200, SWH-3000
a,
SWH-3100
a
125 mA
Multi-Format Proximity Reader SWH-5000
a
, SWH-5100
a,
125 mA
Contactless Smart Card Reader SWH-2100
a
125 mA
Auxiliary Relay Module ARM-1
a
20 mA (relay active)
RM with HID iClass RM1-IC, RM2-IC 300 mA max
RM with HID iClass and LCD RM2L-IC 300 mA max
NOTE
In Table 3-6, an
a
indicates readers that have not been evaluated for use
with iSTAR eX. All other readers in Table 3-6 are UL Listed compatible
readers that can be used with iSTAR eX.