Single Master and Alternate Master Configurations
2–8 iSTAR eX Installation and Configuration Guide
Single Master Configurations
Table 2.1 shows possible ethernet connections for clusters that use a single
master controller.
If a secondary connection is used and the primary connection fails, the system
will automatically switch to the secondary connection.
Alternate Master Configurations
Clusters that use an alternate master use onboard ethernet connections for
both master and alternate as shown in Table 2.2. Dial up and serial
connections are not supported.
The master controller connects to the host over the primary cluster
communication path. The secondary cluster path to the Alternate master is
used if Master or primary path fails.
Table 2.1: Ethernet Connections
Primary Cluster Path Secondary Cluster Path
Master - Onboard 1 N/A
Master - Onboard 2 N/A
Master - Onboard 1 Master - Onboard 2
Master - Onboard 2 Master - Onboard 1
Table 2.2: Ethernet Connections
Primary Cluster Path Secondary Cluster Path
Master - Onboard 1 Alt. Master - Onboard 1
Master - Onboard 1 Alt. Master - Onboard 2
Master - Onboard 2 Alt. Master - Onboard 1
Master - Onboard 2 Alt. Master - Onboard 2