EasyManua.ls Logo

Watlow F4T - Page 122

Watlow F4T
331 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow F4T 119 Chapter 5 Function Reference
PID Set 2 to 3 Crossover
Set the value that will trigger a change (crossover point) from PID set 2 to set 3, relative to the
selected source.
Range: -99,000 to 99,999
PID Set 3 to 4 Crossover
Set the value that will trigger a change (crossover point) from PID set 3 to set 4, relative to the
selected source.
Range: -99,000 to 99,999
PID Set 4 to 5 Crossover
Set the value that will trigger a change (crossover point) from PID set 4 to set 5, relative to
the selected source.
Range: -99,000 to 99,999
Heat Proportional Band [1 to 5]
Set the proportional relationship between heat power (%) and the process value (typically
temperature). This setting determines how big a correction the proportional part of the PID
control algorithm makes when the process value deviates from set point. A smaller propor-
tional band yields a larger power adjustment for a given deviation from set point.
This parameter applies only when Heat Algorithm is set to PID. This parameter is set automat-
ically by autotuning the loop and when TRU-TUNE+ is enabled.
Range: 1 to 99,999 ºF or units
1 to 55,555 ºC
Cool Proportional Band [1 to 5]
Set the proportional relationship between cool power (%) and the process value (typically tem-
perature). This setting determines how big a correction the proportional part of the PID con-
trol algorithm makes when the process value deviates from set point. A smaller proportional
band yields a larger power adjustment for a given deviation from set point.
This parameter applies only when Cool Algorithm is set to PID. This parameter is set automati-
cally by autotuning the loop and when TRU-TUNE+ is enabled.
Range: 3 to 99,999 ºF or units
1 to 55,555 ºC
Integral [1 to 5]
Set how aggressively the integral part of the PID algorithm acts. Integral acts to drive the pro-
cess value to set point by steadily adjusting the output whenever the process value deviates
from the set point. A smaller Time Integral setting yields a larger power adjustment for a giv-
en deviation from set point over a given time.
This parameter applies when either Heat Algorithm or Cool Algorithm or both are set to PID.
This parameter is set automatically by autotuning the loop and when TRU-TUNE+ is enabled.
Range: 0 to 99,999 seconds per repeat

Table of Contents

Other manuals for Watlow F4T

Related product manuals