Watlow F4T 194 Chapter 5 Function Reference
Calibration Offset
Set a value to add to the measured input value to compensate for sensor placement, lead
wire resistance or other factors that cause the input to vary from the actual process value
Range: -99,999.000 to 99,999.000°F or units
-55,555.000 to 55,555.00C
Filter
Set the amount of filtering to apply to the input. Filtering smooths signal fluctuations. In-
crease the time to increase filtering. Excessive filtering slows the inputs response.
Range: 0.0 to 60.0 second
Input Error Latching
Set whether an input error persists until it is cleared or clears automatically when the sensor
signal returns to a normal level.
Options:
Off: error clears automatically once the input returns to normal
On: error remains active until the input returns to normal and the error is cleared by
the Clear Latch parameter
Clear Error
Set this parameter to Clear to reset the input error after correcting the condition that caused
it.
Options: Ignore, Clear

Table of Contents

Other manuals for Watlow F4T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watlow F4T and is the answer not in the manual?

Watlow F4T Specifications

General IconGeneral
InputsThermocouple, RTD, mA, V
OutputsRelay, SSR, mA, V
CommunicationEthernet, Modbus RTU
Data LoggingYes
CertificationsCE, UL, cUL, RoHS
Control ModesPID, On/Off
Power Supply100 to 240 VAC
Operating Temperature0 to 50°C
Enclosure RatingIP65
Display4.3 in. (109 mm) color touch panel LCD
Control LoopsUp to 4

Related product manuals