Watlow F4T 273 Chapter 6 Appendix
Parameter Class
and Name
Range Default
Data Type and
Attributes
Modbus Registers
TC Linearization
"B (11)
C (15)
D (23)
E (26)
F (30)
J (46)
K (48)
N (58)
R (80)
S (84)
T (93)"
J (46)
"unsigned 16-bit
Access = RW"
"Universal Input 1:
Module 1, 27596
Universal Input 1:
Module 2, 28036
Universal Input 1:
Module 3, 28476
Universal Input 1:
Module 4, 28916
Universal Input 1:
Module 5, 29356
Universal Input 1:
Module 6, 29796
Add 110 for the
address of the next
input"
RTD Leads
"2 (1)
3 (2)"
2 (1)
"unsigned 16-bit
Access = RW"
"Universal Input 1:
Module 1, 27598
Universal Input 1:
Module 2, 28038
Universal Input 1:
Module 3, 28478
Universal Input 1:
Module 4, 28918
Universal Input 1:
Module 5, 29358
Universal Input 1:
Module 6, 29798
Add 110 for the
address of the next
input"
Scale Low -100 To 1000 0.0
"IEEE Float
Access=RW"
"Universal Input 1:
Module 1, 27600
Universal Input 1:
Module 2, 28040
Universal Input 1:
Module 3, 28480
Universal Input 1:
Module 4, 28920
Universal Input 1:
Module 5, 29360
Universal Input 1:
Module 6, 29800
Add 110 for the
address of the next
input"
Scale High -100 To 1000 20.0
"IEEE Float
Access=RW"
"Universal Input 1:
Module 1, 27602
Universal Input 1:
Module 2, 28042
Universal Input 1:
Module 3, 28482
Universal Input 1:
Module 4, 28922
Universal Input 1:
Module 5, 29362
Universal Input 1:
Module 6, 29802
Add 110 for the
address of the next
input"