CFW-09-
QUICK PARAMETER REFERENCE
12
Parameters
Function
Adjustable Range
Factory
Unit
User's
Page
Setting
Setting
P165
Speed Filter
0.012 to 1.000
0.012
s
143
P166
Speed Regulator Differential Gain
0.00 to 7.99
0.00 (without
-
143
differential action)
Current Regulator
P167
(4)
Proportional Gain
0.00 to 1.99
0.50
-
143
P168
(4)
Integral Gain
0.000 to 1.999
0.010
-
143
P169
(*) (7)
Maximum Output Current(V/F Control)
(0.2 x P295) to
(1.8 x P295)
1.5 x P295
A
144
P169
(*) (7)
Maximum Forward Torque Current
0 to 180
125
%
144
(Vector Control)
P170
Maximum Reverse Torque Current
0 to 180
125
%
144
(Vector Control)
P171
Maximum Forward Torque Current at
0 to 180
125
%
145
Maximum Speed (P134)
P172
Maximum Reverse Torque Current at
0 to 180
125
%
145
Maximum Speed (P134)
P173
Curve Type of the Max. Torque
0 = Ramp
0 = Ramp
-
145
1 = Step
Flux Regulator
P175
(5)
Proportional Gain
0.0 to 31.9
2.0
-
146
P176
(5)
Integral Gain
0.000 to 9.999
0.020
-
146
P177
Minimum Flux
0 to 120
0
%
146
P178
NominalFlux
0 to 120
100
%
146
P179
Maximum Flux
0 to 120
120
%
146
P180
Field Weakenig Start Point
0 to 120
95
%
146
P181
(1)
Magnetization Mode
0 = General Enable
0 = General Enable
-
146
1 = Start/Stop
CONFIGURATIONPARAMETERS
P200 to P399
Generic Parameters
P200
Password
0 = Off
1 = On
-
147
1 = On
P201
(11)
Language Selection
0 = Português
0, 1, 2, 3
(11)
-
147
1 = English
2 = Español
3 = Deutsch
P202
(1) (2) (11)
Type of Control
0 = V/F 60 Hz
0 (1)
-
147
1 = V/F 50 Hz
2 = V/F Adjustable
3 = Sensorless Vector
4 = Vector with Encoder
5 = VVW (Voltage Vector WEG)
P203
(1)
Special Function Selection
0 = None
0 = None
-
147
1 = PID Regulator
P204
(1) (10)
Load/Save Parameters
0 = Not Used
0 = Not Used
-
148
1 = Not Used
2 = Not Used
3 = Reset P043
4 = Reset P044
5 = Loads Factory Default-60 Hz
6 = Loads Factory Default-50 Hz
(*)
P169 has different function for V/F or Vector Control.

Table of Contents

Other manuals for WEG CFW-09

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WEG CFW-09 and is the answer not in the manual?

WEG CFW-09 Specifications

General IconGeneral
Protection DegreeIP20
Cooling MethodForced ventilation
Power Range0.18 to 11 kW (0.25 to 15 HP)
Frequency Range0 to 400 Hz
Overload Capacity150% for 60 seconds
BrakingDC braking
CommunicationRS485, Modbus RTU
Output Voltage0 to input voltage
Control TypeV/F

Related product manuals