CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
P175 and P176 are automatically set as a function of parameter P412.
In general the automatic setting is adequate and there is no need for a
These gains shall only be manually reconfigured when the excitation
current signal (id*) is oscillating and compromising system operation.
Parameters P177 and P179 define the output limits of the flux regulator
in the Sensorless Vector Control.
The excitation current (id*) may be unstable in case of P175 > 12.
: (id*) can be observed at analog outputs AO3 and /or AO4 by
setting P255 = 14 and / or P257 = 14, or at P029 and / or P030.
These parameters shall not be changed.
P178 is the flux reference to both Vector controls (Sensorless and with
This parameter is representedas a percentage of themotor rated speed
(P402) and defines the speed where the field weakening region of the
If the inverter is operating inVector Control andthe motor is not reaching
its rated speed, itispossible to graduallyreduce thevalue of parameters
P180 and/or P178 until it works appropriately.
Insensorlessvector, magnetizationcurrentispermanentlyON.Todisable
magnetization current when the motor is stopped, program P211 to 1
(ON). This canbe givena time delaybyprogramming P213 greater than
It applies magnetization current after
It applies magnetization current after