EasyManua.ls Logo

WEG CFW-09 - Parameters Related to the Serial Communication

WEG CFW-09
362 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
311
CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES
8.13.5.3
Parameters Related
to the Serial
Communication
Parameternumber
P220
P221
P222
P223
P224
P225
P226
P227
P228
P308
Parameter description
Local/Remote selection
Local reference selection
Remote reference selection
Local forward/reverse selection
Local Start/Stop selection
Local JOG selection
Remote forward/reverse selection
Remote Start/Stop selection
Remote JOG selection
Inverter address on the Serial communication network
(range values from 1 to 30)
2) Inverter:
JOG enabling (provided P225 = 3 to LOC or P228 = 3 to REM)
1) Master:
EOT G STX 0
0
8
0 3
= 0
H
8
H
0
H
8
H
ETX
BCC
C. L. Code
JOG active = 1
add. 7
2) Inverter:
G
ACK
Fault Reset
1) Master:
EOT G STX 0
0
8 0 3 = 8H 0H 8H 0H ETX
BCC
C. L. Code
RESET= 1
add. 7
2) Inverter:
Table 8.22
- Parameters related to the serial communication
G
ACK
G
ACK
For further information aboutthe parameters above, refer to chapter 6 - Detailed
Parameter Description.