CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
NOTE!
The action of loading/saving parameters will take effect only after
P204 has been set and the key is pressed.
P205
0 to 7
Display Default
[ 2 ]
-
Selects which of theparameters listed below will be shown on thedisplay
as a default after the inverter has been powered up:
Range
[Factory Setting]
Parameter
Unit
Description / Notes
6
Load WEG-50 Hz:
Resets all parameters to the 50 Hz
factory default values.
7
Load User 1:
Resets all parameters to the values stored
in Parameter
Memory 1.
8
Load user 2:
Resets all parameters to the value
stored in Parameter Memory 2.
10
Save User 1:
Stores all current inverter parameter
values to Parameter Memory 1.
11
Save User 2:
Stores all current inverter parameter values
to Parameter Memory 2.
P204
Action
0, 1, 2, 9
Not Used:
No action
3
Reset P043:
Resets the Time Enabled hour
meter to zero
4
Reset P044:
Resets the kWh counter to zero
5
Load WEG-60 Hz:
Resets all parameters to the 60 Hz
factory default values.
Table 6.17 -
Action of loading/saving parameters
Table 6.18
- Options displays default
P205
0
1
2
3
4
5
6
7
Display Default
P005 (Motor Frequency)
P003 (Motor Current)
P002 (Motor Speed)
P007 (Motor Voltage)
P006 (Inverter Status)
P009 (Motor Torque)
P070 (Motor Speed and Motor Current)
P040 (PID Process Variable)