CHAPTER 3 - INSTALLATIONANDCONNECTION
The wire sizing indicated in table 3.5 are reference values only. The exact
wire sizing depends on the installation conditions and the maximum
acceptable line voltage drop.
The tightening torque is as indicated in table 3.6. Use 75ÂșC copper wire
- Recommended tightening torque for power and
For protecting the input rectifier diodes and the wiring, use UR Type
(Ultra-Rapid) fuses with i
t equal or lower than indicated in table 3.5.
Standard fuses may be used optionally at the input with currents as
indicated in table 3.5, or circuit breakers dimensioned for 1.2 x rated
inverter input current for the CT or the VT operation (refer to items 9.1.2
However in thiscase, onlythe installation will be protected against short-
circuit, but not the diodes of the rectifier bridge at the inverter input. This
option may damage the inverter in case of short-circuit of some internal