PROSINE 2.0 INVERTER•CHARGER USERS MANUAL
50
445-0089-01-01
Auto Restart After Error
If you select Yes, the inverter•charger will attempt to restart (five
attempts) after a fault has occurred.
If you select No, the inverter•charger ceases operation when an error
occurs. It then requires that you manually restart the unit by going to
the Configuration menu and clearing the error.
Exception: If the inverter•charger shuts down in Invert mode because
of low battery and the charger is enabled and AC is then supplied to
the inverter•charger, it will automatically charge the battery.
Reset to Defaults
You can only apply Load Factory, Save as Custom, or Load Custom if
both the charger and the inverter are disabled. The display panel should
respond with OK. If Error appears, disable invert and charge and try again.
Load Factory
If you select Load Factory, all inverter•charger settings will be reset
to their default values.
Save Custom
If you want to change the settings temporarily, you may want to save
your current system settings. To save the current configuration of the
inverter•charger, select Save Custom. You can then restore this
configuration to the inverter•charger at a later time.
Load Custom
Select Load Custom to restore your custom settings to overwrite the
current PROsine settings.
WARNING
If
Auto Restart
is selected, AC voltage can reappear at the
loads without notice after a fault has occurred and cleared.