SECTION 6 TROUBLESHOOTING
445-0089-01-01
73
Shutdown / Restart Without Error Message
While inverting, the inverter•charger could shut down for a few seconds and
then restart inverting without reporting an error.
This has likely been caused by a reset of the internal microprocessor, which
was probably caused by a discharged and/or weak battery. In particular, this
may occur when the battery is weak and the unit is starting loads which
demand a high surge (e.g. air compressor, air conditioner, fridge).
You can try recharging the battery bank. If the problem persists, an equalize
cycle (only on batteries which permit equalization) may help. If this does not
correct the situation, the battery bank may require upgrading or replacement.