6.16 Adjusting the Motor Current Detection Signal Offset
6.16.2 Manual Adjustment
6-99
6
Application Functions
Preparations
The following conditions must be met to manually adjust the motor current detection signal off-
set.
The parameters must not be write prohibited.
Applicable Tools
The following table lists the tools that you can use to manually adjust the offset and the applica-
ble tool functions.
Operating Procedure
Use the following procedure.
1.
Operate the motor at approximately 100 min
-1
.
2.
Select Setup - Adjust Offset - Adjust the Motor Current Detection Offset. from the
menu bar of the Main Window of the SigmaWin+.
3.
Click the Continue Button.
4.
Click the Manual Adjustment Tab in the Adjust the Motor Current Detection Offset Dia-
log Box.
5.
Set the Channel Box in the Motor Current Detection Offset Area to U-phase.
Tool Function Operating Procedure Reference
Panel Operator Fn00F
13.4.14 Manually Adjust Motor Current Detection Sig-
nal Offset (Fn00F) on page 13-20
Digital Operator Fn00F
Σ-7-Series Digital Operator Operating Manual (Man-
ual No.: SIEP S800001 33)
SigmaWin+
Setup - Adjust Offset -
Adjust the Motor Current
Detection Offset
Operating Procedure on page 6-99