12.11 o: Keypad-Related Settings
1046 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
o2-07: Keypad RUN Direction @ Power-up
No.
(Hex.)
Name Description
Default
(Range)
o2-07
(0527)
Keypad RUN Direction @
Power-up
Sets the direction of motor rotation when the drive is energized and the keypad is the Run command
source.
0
(0, 1)
This parameter is enabled in these conditions:
When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
In LOCAL Mode
0 : Forward
1 : Reverse
o2-09: Reserved
No.
(Hex.)
Name Description
Default
(Range)
o2-09
(050D)
Reserved - -
o2-23: External 24V Powerloss Detection
No.
(Hex.)
Name Description
Default
(Setting Range)
o2-23
(11F8)
RUN
External 24V Powerloss
Detection
Sets the function to give a warning if the backup external 24 V power supply turns off when the main
circuit power supply is in operation.
0
(0, 1)
Note:
The drive will not run when it is operating from one 24-Vexternal power supply.
0 : Disabled
The drive does not detect the loss of the 24-V external power supply.
1 : Enabled
The keypad shows the L24v [Loss of External Power 24 Supply] indicator if the drive detects the loss of the 24-V
external power supply.
Note:
A minor fault signal is not output from H2-xx = 10 [MFDO Function Selection = Alarm].
o2-24: LED Light Function Selection
No.
(Hex.)
Name Description
Default
(Setting Range)
o2-24
(11FE)
LED Light Function
Selection
Sets the function to show the LED status rings and keypad LED lamps.
2
(0 - 2)
Note:
When you initialize the drive with parameter A1-03 [Initialize Parameters], the drive will not reset this parameter.
0 : Enable Status Ring & Keypad LED
1 : LED Status Ring Disable
2 : Keypad LED Light Disable
o2-26: Alarm Display at Ext. 24V Power
No.
(Hex.)
Name Description
Default
(Range)
o2-26
(1563)
Alarm Display at Ext. 24V
Power
When you connect a backup external 24 V power supply, this parameter sets the function to trigger
an alarm when the main circuit power supply voltage decreases.
1
(0, 1)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals