Parameter Details
12
12.11 o: Keypad-Related Settings
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 1045
Drive Model o2-04 Setting
4103 00A3
4140 00A4
4168 00A5
4208 00A6
4250 00A7
4302 00A8
Drive Model o2-04 Setting
4371 00A9
4414 00AA
4477 00AC
4568 00AD
4605 00AE
4720 00AF
Table 12.76 6-Phase/12-Pulse 400 V Class
Drive Model o2-04 Setting
T103 01A3
T140 01A4
T168 01A5
T208 01A6
T250 01A7
T302 01A8
Drive Model o2-04 Setting
T371 01A9
T414 01AA
T477 01AC
T568 01AD
T605 01AE
T720 01AF
o2-05: Home Mode Freq Ref Entry Mode
No.
(Hex.)
Name Description
Default
(Setting Range)
o2-05
(0509)
Home Mode Freq Ref Entry
Mode
Sets the function that makes it necessary to push to use the keypad to change the frequency
reference value while in Drive Mode.
0
(0, 1)
0 : ENTER Key Required
You must push to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is not
necessary to push . The drive keeps the frequency reference for 5 seconds after you use and on the
keypad to change the frequency reference value.
o2-06: Keypad Disconnect Detection
No.
(Hex.)
Name Description
Default
(Range)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
1
(0, 1)
This parameter continues to operate if the keypad installed to the drive becomes disconnected.
This parameter is enabled in these conditions:
When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
In LOCAL Mode
0 : Disabled
The drive continues operation when it detects a keypad disconnection.
1 : Enabled
The drive stops operation, detects oPr [Keypad Connection Fault], and the motor coasts to stop when the drive
detects a keypad disconnection.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV