12.11 o: Keypad-Related Settings
1054 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Table 12.78 Unit Codes
Unit Code (Hex.) Unit Unit Code (Hex.) Unit Unit Code (Hex.) Unit Unit Code (Hex.) Unit
00 08 PPR 10 H 18 0H
01 Hz 09 kW 11 V 19
02 RPM 0A Ω 12 us 1A
03 % 0B ms 13 min 1B
04 VAC 0C kHz 14 °C 1C
05 VDC 0D PSI 15 W 1D
06 A 0E MPM 16 kWH 1E
07 sec 0F FPM 17 MWH 1F
Third and Subsequent Rows: Log Data
This example shows the data text strings and data generated for the third row of log data.
Example of generated data:
02,0012,160107111239,1770,1770,00BE,0118,0028,0000,0000,0000,0000,0000,0000,0000,00000C
No. Item
Number of
Characters
Description
1 Attribute 2 [02] shows that the record is a monitor data record.
2 File number 4 Generates the [xxx] part (a 3-digit decimal number) of the [GLOG0xxx.csv] filename of the log data in hexadecimal
format.
3 Time stamp 12 Data log data was retrieved (YYMMDDHHMMSS)
4 Log Monitor Data 1 4 Log monitor data (Hex.) of the monitor selected with o5-03 [Log Monitor Data 1]
5 Log Monitor Data 2 4 Log monitor data (Hex.) of the monitor selected with o5-04 [Log Monitor Data 2]
: : : :
13 Log Monitor Data 10 4 Log monitor data (Hex.) of the monitor selected with o5-12 [Log Monitor Data 10]
14 Reserved 4 -
15 Encoding data 4 Log Monitor Data 1 to 10 Code Data (Hex.)
Bits 0 to 9 show the encoding of log monitor data 1 to 10. A bit value of 1 shows that the data represents a negative value.
(Log monitor data 1 to 10 are absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have values of 1, and the encoding data
= 0010010010 (Bin.) = 0092 (Hex.)
16 Row number 6 Row number (Hex.) in the data log file
o5-01: Log Start/Stop Selection
No.
(Hex.)
Name Description
Default
(Range)
o5-01
(1551)
RUN
Log Start/Stop Selection
Sets the data log function. This parameter is only available when using an LCD keypad.
0
(0 - 1)
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
o5-02: Log Sampling Interval
No.
(Hex.)
Name Description
Default
(Range)
o5-02
(1552)
RUN
Log Sampling Interval
Sets the data log sampling cycle. This parameter is only available when using an LCD keypad.
100 ms
(100 - 60000 ms)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV