Startup Procedure and Test Run
4
4.8 Auto-Tuning
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 217
Mode Parameter Settings Application Conditions and Benefits
Applicable Control Method
(A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
CLV/PM
(7)
PM Rotational Auto-Tuning T2-01 = 4
When the information from the motor test report or
motor nameplate is not available.
When you can decouple the motor and load the motor
can rotate freely while Auto-Tuning.
Values measured during Auto-Tuning are
automatically set to the motor parameters.
x x x
High Frequency Injection Auto-
Tuning
T2-01 = 5
Automatically determines the control parameters
required to set n8-35 = 1 [Initial Pole Detection
Method = High Frequency Injection] or n8-57 = 1
[HFI Overlap Selection = Enabled].
Applicable to IPM motors only.
Perform tuning with the motor connected to the drive.
Note:
When you want to set n8-35 = 1 or n8-57 = 1,
perform High Frequency Injection Auto-Tuning.
Configure the drive with the data from the motor
nameplate before performing High Frequency
Injection Auto-Tuning. High Frequency Injection
Auto-Tuning automatically makes adjustments while
it is stopped but still energized.
x x x
Input Data for PM Motor Auto-Tuning
To do Auto-Tuning, input data for the items in Table 4.9 and Table 4.10 that have an "x". Before starting Auto-
Tuning, prepare the motor test report or record the information on the motor nameplate as a reference.
Table 4.9 Input Data for PM Motor Auto-Tuning
Input Data Parameter Unit
Auto-Tuning Mode
(T2-01 Setting)
PM Motor Parameter Settings
(0)
PM Stationary
Auto-Tuning
(1)
PM Stationary Auto-
Tuning for Stator
Resistance
(2)
Control method selection A1-02 - 5, 6, 7 5 6, 7 5 6, 7 5, 6, 7
PM Motor Code Selection T2-02 -
Motor code of Yaskawa
motor
*1
FFFF
*2
FFFF
*2
- - -
PM Motor Type T2-03 - - - - x x -
PM Motor Rated Power T2-04 kW - x x x x -
PM Motor Rated Voltage T2-05 V - x x x x -
PM Motor Rated Current T2-06 A - x x x x x
PM Motor Base Frequency T2-07 Hz - x - x - -
Number of PM Motor Poles T2-08 - - x x x x -
PM Motor Base Speed T2-09 min
-1
- - x - x -
PM Motor Stator Resistance T2-10 Ω x x x - - -
PM Motor d-Axis Inductance T2-11 mH x x x - - -
PM Motor q-Axis Inductance T2-12 mH x x x - - -
Back-EMF Units Selection T2-13 - x x x - - -
Back-EMF Voltage Constant
(Ke)
T2-14
*3
x x x - - -
Pull-In Current Level T2-15 % - - - x x -
Encoder Pulse Count (PPR) T2-16 -
*4
-
*4
-
*4
-
Encoder Z-Pulse Offset for
PM Motor
T2-17 Degrees
*4
-
*4
-
*4
-
*1 Set the motor code for a Yaskawa PM motor.
*2 Set the motor code to FFFF for a PM motor from a different manufacturer.
*3 Changes when the value set in T2-13 changes.
*4 Input this value when A1-02 = 7 [Control Method Selection = PM Closed Loop Vector Control].