5.2 European Standards
268 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
A - Grounding surface (Remove any paint or sealant.)
B - Enclosure panel
C - Metal plate
D - Drive
E - Ground the shield.
F - Motor
G - Motor cable (Braided shield cable: 10 m (32.8 ft)
maximum)
H - Cable clamp
I - Grounding wire
J - EMC noise filter
Figure 5.19 EMC Noise Filter and Drive Installation Procedure
5. Connect the DC link choke to decrease harmonic distortion. Refer to DC Link Chokes on page 270 to select a
DC link choke.
Note:
• To maintain compliance with IEC/EN 61000-3-2 on drive models 2004, 2006, 4002, and 4004, install a DC link choke.
• The terminal block for the drive main circuit and the terminal block for the DC link choke have different shapes. The drive has a
European-style terminal block, and the DC link choke has a round terminal block. Correctly prepare the ends of the wiring.
• Ground the DC link choke (option) on the back of the mounting base. Remove all paint from the mounting surface of the control
panel.