Standards Compliance
5
5.2 European Standards
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 267
Note:
Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
The maximum wiring length between the drive and motor is 10 m (32.8 ft). Keep the wire as short as possible.
Keep the grounding wire as short as possible.
4. Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications and local safety standards.
A - Braided shield cable
B - Metal plate
C - Cable clamp (conductive)
Figure 5.18 Ground the Shield