Standards Compliance
5
5.3 UL Standards
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 277
Model Terminal
Recomm. Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
(mm
2
)
IP20 Applicable
Gauge
*1
AWG, kcmil
(mm
2
)
Wire Stripping
Length
*2
mm
Terminal Screw
Size and Shape
Tightening
Torque
N∙m (lbf∙in)
2211
R/L1, S/L2, T/L3 250
2 - 250
(35 - 120)
2/0 - 250
(70 - 120)
37
M10
12 - 14
(107 - 124)
U/T1, V/T2, W/T3 300
2 - 300
(35 - 150)
3/0 - 300
(95 - 150)
37
M10
12 - 14
(107 - 124)
-, -, +1, +1
*4 *5
2/0
6 - 2/0
(16 - 70)
1/0 - 2/0
(50 - 70)
28
M6
8 - 9
(71 - 80)
+3
*5
2/0
4 - 2/0
(25 - 70)
1 - 2/0
(35 - 70)
28
M8
8 - 9
(71 - 80)
4
4 - 1/0
(25 - 50)
- -
M8
9.0 - 11
(79.7 - 97.4)
2257
R/L1, S/L2, T/L3 2/0 × 2P
3 - 4/0 × 2P
(25 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
U/T1, V/T2, W/T3 2/0 × 2P
3 - 4/0 × 2P
(25 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
-, +1 4/0 × 2P
2 - 250 × 2P
(35 - 120 × 2P)
4/0 - 250 × 2P
(95 × 2P)
-
M10
20
(177)
+3 1/0 × 2P
4 - 1/0 × 2P
(25 - 50 × 2P)
1/0 × 2P
(50 × 2P)
-
M10
20
(177)
3
3 - 350
(25 - 185)
- -
M10
18 - 23
(159 - 204)
2313
R/L1, S/L2, T/L3 4/0 × 2P
3 - 4/0 × 2P
(25 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
U/T1, V/T2, W/T3 3/0 × 2P
3 - 4/0 × 2P
(25 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
-, +1 250 × 2P
2 - 250 × 2P
(35 - 120 × 2P)
4/0 - 250 × 2P
(95 × 2P)
-
M10
20
(177)
+3 1/0 × 2P
4 - 1/0 × 2P
(25 - 50 × 2P)
1/0 × 2P
(50 × 2P)
-
M10
20
(177)
2
2 - 350
(35 - 150)
- -
M10
18 - 23
(159 - 204)
2360
R/L1, S/L2, T/L3 250 × 2P
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
35
(310)
U/T1, V/T2, W/T3 250 × 2P
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
35
(310)
-, +1 350 × 2P
4/0 - 400 × 2P
(95 - 185 × 2P)
300 - 400 × 2P
(150 - 185 × 2P)
-
M12
35
(310)
+3 3/0 × 2P
1/0 - 4/0 × 2P
(50 - 95 × 2P)
- -
M12
35
(310)
1
1 - 350
(50 - 150)
- -
M12
32 - 40
(283 - 354)
2415
R/L1, S/L2, T/L3 250 × 2P
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
35
(310)
U/T1, V/T2, W/T3 300 × 2P
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
35
(310)
-, +1 350 × 2P
4/0 - 400 × 2P
(95 - 185 × 2P)
300 - 400 × 2P
(150 - 185 × 2P)
-
M12
35
(310)
+3 3/0 × 2P
1/0 - 4/0 × 2P
(50 - 95 × 2P)
- -
M12
35
(310)
1
1 - 350
(50 - 150)
- -
M12
32 - 40
(283 - 354)
*1 For IP20 protection, use wires that are in the range of applicable gauges.
*2 Remove insulation from the ends of wires to expose the length of wire shown.