EasyManua.ls Logo

YASKAWA GA800 - Page 338

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.3 MEMOBUS/Modbus Communications
338 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Register No.
(Hex.)
Description
00C5
Fault Description 8
bit 0 LSo [Low Speed Motor Step-Out]
bit 1 nSE [Node Setup Error]
bit 2 - 9 Reserved
bit A dv7 [Polarity Judge Timeout]
bit B - F Reserved
00C6 - 00C7 Reserved
00C8
Minor Fault Description 2
bit 0 Uv [Undervoltage]
bit 1 ov [Overvoltage]
bit 2 oH [Heatsink Overheat]
bit 3 Overheat Alarm (oH2)
bit 4 oL3 [Overtorque 1]
bit 5 oL4 [Overtorque 2]
bit 6 EF [FWD/REV Run Command Input Error]
bit 7 bb [Baseblock]
bit 8 EF3 [External Fault (Terminal S3)]
bit 9 EF4 [External Fault (Terminal S4)]
bit A EF5 [External Fault (Terminal S5)]
bit B EF6 [External Fault (Terminal S6)]
bit C EF7 [External Fault (Terminal S7)]
bit D EF8 [External Fault (Terminal S8)]
bit E FAn [Internal Fan Fault]
bit F oS [Overspeed]
00C9
Minor Fault Description 3
bit 0 dEv [Speed Deviation]
bit 1 PGo [Encoder (PG) Feedback Loss]
bit 2 oPr [Keypad Connection Fault]
bit 3 CE [Modbus Communication Error]
bit 4 bUS [Option Communication Error]
bit 5 CALL [Serial Comm Transmission Error]
bit 6 oL1 [Motor Overload]
bit 7 oL2 [Drive Overload]
bit 8 Reserved
bit 9 EF0 [Option Card External Fault]
bit A rUn [Motor Switch during Run]
bit B Reserved
bit C CALL [Serial Comm Transmission Error]
bit D UL3 [Undertorque Detection 1]
bit E UL4 [Undertorque Detection 2]
bit F SE [Modbus Test Mode Error]