EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Network Communications
6
6.3 MEMOBUS/Modbus Communications
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 339
Register No.
(Hex.)
Description
00CA
Minor Fault Description 4
bit 0 L24v [Loss of External Power 24 Supply]
bit 1 oH3 [Motor Overheat (PTC Input)]
bit 2 - 5 Reserved
bit 6 FbL [PID Feedback Loss]
bit 7 FbH [Excessive PID Feedback]
bit 8 Reserved
bit 9 dnE [Drive Disabled]
bit A PGoH [Encoder (PG) Hardware Fault]
bit B - F Reserved
00CB
Minor Fault Description 5
bit 0 E5 [MECHATROLINK Watchdog Timer Err]
bit 1 AEr [Station Address Setting Error]
bit 2 CyC [MECHATROLINK CommCycleSettingErr]
bit 3 HCA [High Current Alarm]
bit 4 LT-1 [Cooling Fan Maintenance Time]
bit 5 LT-2 [Capacitor Maintenance Time]
bit 6 - 7 Reserved
bit 8 EF1 [External Fault (Terminal S1)]
bit 9 EF2 [External Fault (Terminal S2)]
bit A SToF [Safe Torque OFF Hardware]
bit B STo [Safe Torque OFF]
bit C oL5 [Mechanical Weakening Detection 1]
bit D UL5 [Mechanical Weakening Detection 2]
bit E - F Reserved
00CC
Minor Fault Description 6
bit 0 Reserved
bit 1 TrPC [IGBT Maintenance Time (90%)]
bit 2 LT-3 [SoftChargeBypassRelay MainteTime]
bit 3 LT-4 [IGBT Maintenance Time (50%)]
bit 4 boL [Braking Transistor Overload]
bit 5 - 7 Reserved
bit 8 dWAL [DriveWorksEZ Fault]
bit 9 - F Reserved
00CD - 00CF Reserved

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals