Parameter List
11
11.9 F: Options
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 581
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F7-14
(03F2)
Duplex Mode Selection
Sets the duplex mode setting method.
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
4 : Half/Full
5 : Auto/Half
6 : Auto/Full
7 : Full/Half
8 : Full/Auto
1
(0 - 8)
876
F7-15
(03F3)
Communication Speed
Selection
Sets the communications speed.
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
10
(10, 100 - 102)
876
F7-16
(03F4)
Timeout Value
Sets the detection time for a communications timeout.
Note:
Set this parameter to 0.0 to disable the connection timeout function.
0.0 s
(0.0 - 30.0 s)
877
F7-17
(03F5)
EtherNet/IP Speed
Scaling Factor
Sets the scaling factor for the speed monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
877
F7-18
(03F6)
EtherNet/IP Current Scale
Factor
Sets the scaling factor for the output current monitor in the EtherNet/IP Class ID 2AH
Object.
0
(-15 - +15)
877
F7-19
(03F7)
EtherNet/IP Torque Scale
Factor
Sets the scaling factor for the torque monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
877
F7-20
(03F8)
EtherNet/IP Power
Scaling Factor
Sets the scaling factor for the power monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
877
F7-21
(03F9)
EtherNet/IP Voltage Scale
Factor
Sets the scaling factor for the voltage monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
877
F7-22
(03FA)
EtherNet/IP Time Scaling
Sets the scaling factor for the time monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
877
F7-23
(03FB)
Dynamic Out Param 1 for
CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the
values from Output Assembly 116 to the MEMOBUS/Modbus address register that is
stored for each parameter. The drive will not write the values from Output Assembly 116
to the registers when the MEMOBUS/Modbus address is 0. When you use a PROFINET
option, set this parameter to set to configurable output 1.
0 878
F7-24
(03FC)
Dynamic Out Param 2 for
CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the
values from Output Assembly 116 to the MEMOBUS/Modbus address register that is
stored for each parameter. The drive will not write the values from Output Assembly 116
to the registers when the MEMOBUS/Modbus address is 0. When you use a PROFINET
option, set this parameter to set to configurable output 2.
0 878
F7-25
(03FD)
Dynamic Out Param 3 for
CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the
values from Output Assembly 116 to the MEMOBUS/Modbus address register that is
stored for each parameter. The drive will not write the values from Output Assembly 116
to the registers when the MEMOBUS/Modbus address is 0. When you use a PROFINET
option, set this parameter to set to configurable output 3.
0 878
F7-26
(03FE)
Dynamic Out Param 4 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 4.
0 878
F7-27
(03FF)
Dynamic Out Param 5 for
CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the
values from Output Assembly 116 to the MEMOBUS/Modbus address register that is
stored for each parameter. The drive will not write the values from Output Assembly 116
to the registers when the MEMOBUS/Modbus address is 0. When you use a PROFINET
option, set this parameter to set to configurable output 5.
0 878