11.9 F: Options
582 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F7-28
(0370)
Dynamic Out Param 6 for
CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the
values from Output Assembly 116 to the MEMOBUS/Modbus address register that is
stored for each parameter. The drive will not write the values from Output Assembly 116
to the registers when the MEMOBUS/Modbus address is 0.
0 878
F7-29
(0371)
Dynamic Out Param 7 for
CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the
values from Output Assembly 116 to the MEMOBUS/Modbus address register that is
stored for each parameter. The drive will not write the values from Output Assembly 116
to the registers when the MEMOBUS/Modbus address is 0.
0 878
F7-30
(0372)
Dynamic Out Param 8 for
CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the
values from Output Assembly 116 to the MEMOBUS/Modbus address register that is
stored for each parameter. The drive will not write the values from Output Assembly 116
to the registers when the MEMOBUS/Modbus address is 0.
0 878
F7-31
(0373)
Dynamic Out Param 9 for
CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the
values from Output Assembly 116 to the MEMOBUS/Modbus address register that is
stored for each parameter. The drive will not write the values from Output Assembly 116
to the registers when the MEMOBUS/Modbus address is 0.
0 878
F7-32
(0374)
Dynamic Out Param 10
for CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the
values from Output Assembly 116 to the MEMOBUS/Modbus address register that is
stored for each parameter. The drive will not write the values from Output Assembly 116
to the registers when the MEMOBUS/Modbus address is 0.
0 878
F7-33
(0375)
Dynamic In Param 1 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 1.
0 878
F7-34
(0376)
Dynamic In Param 2 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 2.
0 878
F7-35
(0377)
Dynamic In Param 3 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 3.
0 878
F7-36
(0378)
Dynamic In Param 4 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 4.
0 878
F7-37
(0379)
Dynamic In Param 5 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 5.
0 878
F7-38
(037A)
Dynamic In Param 6 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
0 878
F7-39
(037B)
Dynamic In Param 7 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
0 878
F7-40
(037C)
Dynamic In Param 8 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
0 878