11.10 H: Terminal Functions
602 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Setting Value Function Description Ref.
101 !Zero Speed
The terminal deactivates when the output frequency is less than E1-09 [Minimum Output Frequency] or b2-01 [DC
Injection/Zero SpeedThreshold].
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting Description Parameter Used as the Reference
0 Open Loop V/f Control E1-09
1 V/f Control with Encoder E1-09
2 Open Loop Vector b2-01
3 Closed Loop Vector E1-09
4 Advanced OpenLoop Vector Control E1-09
5 PM Open Loop Vector Control E1-09
6 PM Advanced Open Loop Vector E1-09
7 PM Closed Loop Vector Control b2-01
8 EZ Open Loop Vector Control E1-09
ON : The output frequency is the value of E1-09 or more, or b2-01 or more.
OFF : The output frequency is less than the value of E1-09 or b2-01.
929
102 !Speed Agree 1
The terminal deactivates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree
Detection Width].
Note:
In CLV, the motor speed is the reference.
ON : The output frequency does not align with the frequency reference although the drive is running.
OFF : The output frequency is in the range of frequency reference ± L4-02.
929
103 !User-Set Speed Agree 1
The terminal deactivates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02
[Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
When using Closed Loop Vector Control, this is the value of Motor Speed ± L4-02.
ON : The output frequency is not in the range of L4-01 ± L4-02 nor the range of frequency reference ± L4-02.
OFF : The output frequency is in the range of L4-01 ± L4-02 and the range of frequency reference ± L4-02.
929
104 !Frequency Detection 1
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level] +
L4-02 [Speed Agree Detection Width]. When the terminal activates, it stays activated until the output frequency = L4-
01.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
In CLV, the motor speed is the reference.
ON : The output frequency is higher than L4-01 + L4-02.
OFF : The output frequency is less than L4-01 or is not more than L4-01 + L4-02.
929
105 !Frequency Detection 2
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level].
When the terminal deactivates, it stays deactivated until the output frequency = L4-01 - L4-02.
ON : The output frequency is less than L4-01 - L4-02, or it is not more than L4-01.
OFF : The output frequency is more than L4-01.
929
106 !Drive Ready
The terminal deactivates when the drive is ready and running.
929
107 !DC Bus Undervoltage
The terminal deactivates when the DC bus voltage or control circuit power supply is at or below the voltage set in L2-
05 [Undervoltage Detection Lvl (Uv1)]. The terminal also deactivates when there is a fault with the DC bus voltage.
ON : The DC bus voltage is more than the setting value of L2-05.
OFF : The DC bus voltage is less than the setting value of L2-05.
929
108 During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
929
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV