Parameter List
11
11.10 H: Terminal Functions
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 601
Setting Value Function Description Ref.
62 Modbus Reg 1 Status
Satisfied
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register
address set with H2-07 [Modbus Register 1 Address Select] activates.
927
63 Modbus Reg 2 Status
Satisfied
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register
address set with H2-09 [Modbus Register 2 Address Select] activates.
927
65 Standby Output
The terminal deactivates after the drive stops operating and after the time set with b8-51 [Standby Mode Wait Time].
ON : The Run command turns on and the magnetic contactor on the input side turns on.
OFF : The Run command turns off and the drive stops operating. Then, the magnetic contactor on the input side turns
off after the time set in b8-51 [Standby Mode Wait Time] elapses.
927
66 Comparator1
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the values
of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24 [Comparator
1 On-Delay Time].
927
67 Comparator2
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of the
values of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-30
[Comparator 2 On-Delay Time].
928
69 External Power 24V
Supply
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : The external 24V power supply is supplying power.
OFF : The external 24V power supply is not supplying power.
928
6A Data Logger Error
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
929
90 DWEZ Digital Output 1
Sets the DriveWorksEZ digital output 1. Refer to the DriveWorksEZ online manual for more information.
929
91 DWEZ Digital Output 2
Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.
929
92 DWEZ Digital Output 3
Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.
929
93 DWEZ Digital Output 4
Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.
929
A0 DWEZ Extended Digital
Output 1
Sets the DriveWorksEZ digital output 1. Refer to the DriveWorksEZ online manual for more information.
929
A1 DWEZ Extended Digital
Output 2
Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.
929
A2 DWEZ Extended Digital
Output 3
Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.
929
A3 DWEZ Extended Digital
Output 4
Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.
929
A4 DWEZ Extended Digital
Output 5
Sets the DriveWorksEZ digital output 5. Refer to the DriveWorksEZ online manual for more information.
929
A5 DWEZ Extended Digital
Output 6
Sets the DriveWorksEZ digital output 6. Refer to the DriveWorksEZ online manual for more information.
929
A6 DWEZ Extended Digital
Output 7
Sets the DriveWorksEZ digital output 7. Refer to the DriveWorksEZ online manual for more information.
929
A7 DWEZ Extended Digital
Output 8
Sets the DriveWorksEZ digital output 8. Refer to the DriveWorksEZ online manual for more information.
929
100 !During Run
The terminal deactivates when you input a Run command and when the drive is outputting voltage.
ON : Drive is stopping
OFF : Drive is running
929