Parameter List
11
11.20 Parameters Changed by E1-03 [V/f Pattern Selection]
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 671
Table 11.3 Parameters Changed by E1-03: 2257 to 2415 (HD), 2211 to 2415 (ND), 4140 to 4720 (HD), 4103 to 4720 (ND), and
T140 to T720 (HD), T103 to T720 (ND)
No. E1-03 E1-04 E1-05
*1
E1-06 E1-07 E1-08
*1
E1-09 E1-10
*1
Unit - Hz V Hz Hz V Hz V
Setting Value
0 50.0 230.0 50.0 2.5 13.8 1.3 6.9
1 60.0 230.0 60.0 3.0 13.8 1.5 6.9
2 60.0 230.0 50.0 3.0 13.8 1.5 6.9
3 72.0 230.0 60.0 3.0 13.8 1.5 6.9
4 50.0 230.0 50.0 25.0 40.3 1.3 5.8
5 50.0 230.0 50.0 25.0 57.5 1.3 6.9
6 60.0 230.0 60.0 30.0 40.3 1.5 5.8
7 60.0 230.0 60.0 30.0 57.5 1.5 6.9
8 50.0 230.0 50.0 2.5 17.3 1.3 8.1
9 50.0 230.0 50.0 2.5 23.0 1.3 10.4
A 60.0 230.0 60.0 3.0 17.3 1.5 8.1
B 60.0 230.0 60.0 3.0 23.0 1.5 12.7
C 90.0 230.0 60.0 3.0 13.8 1.5 6.9
D 120.0 230.0 60.0 3.0 13.8 1.5 6.9
E 180.0 230.0 60.0 3.0 13.8 1.5 6.9
F 60.0
*2
230.0
*2
60.0
*2
3.0
*2
13.8
*2
1.5
*2
6.9
*2
Control Method
Selection
(A1-02 Setting)
OLV (2) 60.0 230.0 60.0 3.0 12.7 0.5 2.3
CLV (3) 60.0 230.0 60.0 0.0 0.0 0.0 0.0
OLV/PM (5)
*3 *3 *3
- -
*3
-
AOLV/PM (6)
*3 *3 *3
- -
*3
-
CLV/PM (7)
*3 *3 *3
- - 0.0 -
*1 This is the value for 200 V class drives. Double the value for 400 V class drives.
*2 These values are the default settings for E1-04 to E1-10 and E3-04 to E3-10 [V/f Pattern for Motor 2]. These settings are the same as
those for the V/f pattern when E1-03 = 1 [Const Trq, 60Hz base, 60Hz max].
*3 The default setting varies depending on the setting of E5-01 [PM Motor Code Selection].