Parameter List
11
11.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 687
No.
*1
Name Unit Default
- Drive Model - 4168 4208 4250 4302
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 00A5 00A6 00A7 00A8
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
100
(75)
125
(90)
125
(90)
150
(110)
150
(110)
200
(150)
200
(150)
250
(185)
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 30 30 30 30 30 30 30 30
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.533 0.592 0.592 0.646 0.646 0.673 0.673 0.777
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 4371 4414 4477 4568
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 00A9 00AA 00AC 00AD
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
250
(185)
300
(220)
300
(220)
350
(260)
350
(260)
400
(300)
400
(300)
450
(335)
b3-04
V/f Gain
during Speed
Search
% 60 60 60 60 60 60 60 60
b3-06
Speed
Estimation
Current Level
1
- 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Speed
Estimation
ACR P Gain
- 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
b8-04
Energy Saving
Coefficient
Value
- 30.13 30.57 30.57 27.13 27.13 21.76 21.76 21.76
C5-17
(C5-37)
Motor Inertia kgm
2
3.30 3.60 3.60 4.10 4.10 6.50 6.50 11.00
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 270 310 310 370 370 500 500 500