12.2 A: Initialization Parameters
702 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
No.
(Hex.)
Name Description
Default
(Range)
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0
(0 - 5)
The drive software contains the application presets shown below. Set A1-06 to align with the application to let the
drive automatically set the best parameter settings for the selected application. The drive saves parameters frequently
used for the application in parameters A2-01 to A2-16 [User Parameters 1 to 16] for easy configuration and reference
in [User Custom Parameters] in the main menu.
Water supply pump
Conveyor
Exhaust fan
HVAC fan
Air compressor
Note:
Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization] to
initialize parameters.
It is not possible to change the A1-06 value. To set an application preset, first set A1-03 = 2220 to initialize parameters, then set this
parameter. If initializing all parameters will cause a problem, do not change the settings.
If you set A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms] to set parameters to A2-17 to A2-32 [User
Parameters 17 to 32] automatically, the drive will reset these parameters when you change the A1-06 setting.
0 : General-purpose
The drive saves the parameters in Table 12.3 as user parameters.
Table 12.3 Parameters Saved as User Parameters with the General-purpose Preset
User Parameter No. Parameter No. Saved Name
A2-01
A1-02 Control Method Selection
A2-02
b1-01 Frequency Reference Selection 1
A2-03
b1-02 Run Command Selection 1
A2-04
b1-03 Stopping Method Selection
A2-05
C1-01 Acceleration Time 1
A2-06
C1-02 Deceleration Time 1
A2-07
C6-01 Normal / Heavy Duty Selection
A2-08
C6-02 Carrier Frequency Selection
A2-09
d1-01 Reference 1
A2-10
d1-02 Reference 2
A2-11
d1-03 Reference 3
A2-12
d1-04 Reference 4
A2-13
d1-17 Jog Reference
A2-14
E1-01 Input AC Supply Voltage
A2-15
E1-03 V/f Pattern Selection
A2-16
E1-04 Maximum Output Frequency
A2-17 E1-05 Maximum Output Voltage
A2-18 E1-06 Base Frequency
A2-19 E1-09 Minimum Output Frequency
A2-20 E1-13 Base Voltage
A2-21 E2-01 Motor Rated Current (FLA)
A2-22 E2-04 Motor Pole Count
A2-23 E2-11 Motor Rated Power
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV