Parameter Details
12
12.3 b: Application
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 725
The drive accepts a Run command entered from an external source when setting the parameters in Programming
Mode.
2 : Allow Programming Only at Stop
The drive does not allow the user to enter the Programming Mode while the drive is operating. The keypad does not
display the Programming Mode while the drive is operating.
■ b1-09: LOCAL/REMOTE Select during RUN
No.
(Hex.)
Name Description
Default
(Range)
b1-09
(0188)
Expert
LOCAL/REMOTE Select
during RUN
Sets the function that lets you use the during operation to switch between LOCAL and
REMOTE Modes.
0
(0, 1)
0 : Disabled
1 : Enabled
When you switch the operation mode from REMOTE to LOCAL during run, the drive writes this REMOTE operation
status to the keypad:
• Frequency reference during run
• RUN/STOP status of the keypad
• FWD/REV
• JOG
Note:
When b1-09 = 1, the drive will detect oPE05 [Run Cmd/Freq Ref Source Sel Err] if you set one of these parameter values:
• b1-02 = 0 [Run Command Selection 1 = Keypad]
• b1-16 = 0 [Run Command Selection 2 = Keypad] and H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection]
• H1-xx = 3 to 6, 12, 13, 32 [Multi-Step Speed Reference 1 to 4, Jog Reference Selection, Forward Jog, Reverse Jog]
■ b1-14: Phase Order Selection
No.
(Hex.)
Name Description
Default
(Range)
b1-14
(01C3)
Phase Order Selection
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align the
Forward Run command from the drive and the forward direction of the motor without changing
wiring.
0
(0, 1)
0 : Standard
1 : Switch Phase Order
■ b1-15: Frequency Reference Selection 2
No.
(Hex.)
Name Description
Default
(Range)
b1-15
(01C4)
Frequency Reference
Selection 2
Sets the input method for frequency reference 2.
0
(0 - 4)
This parameter is enabled when H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] is
activated.
Note:
• Push on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
• If the frequency reference is 0 Hz or ≤ E1-09 [Minimum Output Frequency] and the drive receives a Run command, the on the keypad
will flash. Check the setting for the frequency reference input and enter a value more than or equal to E1-09.
0 : Keypad
Use the keypad to enter the frequency reference.
Use and on the keypad to change the frequency reference.