12.3 b: Application
726 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
1 : Analog Input
Use MFAI terminals A1, A2, and A3 to input an analog frequency reference with a voltage or current input signal.
Voltage Input
Refer to Table 12.20 to use a voltage signal input to one of the MFAI terminals.
Table 12.20 Frequency Reference Voltage Input
Terminal
Terminal Signal
Level
Parameter Settings
Note
Signal Level
Selection
Function Selection Gain Bias
A1 0 - 10 V H3-01 = 0 H3-02 = 0
[Frequency Reference]
H3-03 H3-04 Set DIP switch S1-1 to
V for voltage input.
-10 - +10 V H3-01 = 1
A2 0 - 10 V H3-09 = 0 H3-10 = 0
[Frequency Reference]
H3-11 H3-12 Set DIP switch S1-2 to
V for voltage input.
-10 - +10 V H3-09 = 1
A3 0 - 10 V H3-05 = 0 H3-06 = 0
[Frequency Reference]
H3-07 H3-08 Set DIP switch S1-3 to
V for voltage input.
Set DIP switch S4 to
AI for analog input.
-10 - +10 V H3-05 = 1
Figure 12.22 Example of Setting the Frequency Reference with a Voltage Signal to Terminal A1
Note:
You can also use this diagram to wire terminals A2 and A3.
Current Input
Refer to Table 12.21 to use a voltage signal input to one of the MFAI terminals.
Table 12.21 Frequency Reference Current Input
Terminal Signal Level
Parameter Settings
Note
Signal Level
Selection
Function Selection Gain Bias
A1 4 mA to 20 mA H3-01 = 2 H3-02 = 0
[Frequency Reference]
H3-03 H3-04 Set DIP switch S1-1 to
I for current input.
0 - 20 mA H3-01 = 3
A2 4 mA to 20 mA H3-09 = 2 H3-10 = 0
[Frequency Reference]
H3-11 H3-12 Set DIP switch S1-2 to
I for current input.
0 - 20 mA H3-09 = 3
A3 4 mA to 20 mA H3-05 = 2 H3-06 = 0
[Frequency Reference]
H3-07 H3-08 Set DIP switch S1-3 to
I for current input.
Set DIP switch S4 to
AI for analog input.
0 - 20 mA H3-05 = 3