Parameter Details
12
12.3 b: Application
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 749
■ EZ Sleep/Wake-up Functionality
Set b5-89 = 1 [Sleep Method Selection = EZ Sleep/Wake-up] to enable the EZ Sleep/Wake-up function.
Note:
• When b5-89 = 0 [Sleep Mode Selection = Standard], the EZ Sleep function and related parameters are disabled. Parameter b5-91 [EZ Sleep
Minimum Speed] is not included in this rule.
• Set b5-89 = 1 to disable b5-15 [PID Sleep Function Start Level].
Setting Parameter Description
b5-90 [EZ Sleep Unit] Sets the unit of measure for b5-92 [EZ Sleep Level]. When b5-90 = 0 [0.1Hz units], the setting range of b5-91
[EZ Sleep Minimum Speed] is 0.0 to 590.0 Hz. When b5-90 = 1 [rev/min], the setting range is 0 to 35400 min-
-1
(r/min).
Note:
When you change b5-90, the value of b5-92 is not automatically updated.
b5-91 [EZ Sleep Minimum Speed]
This parameter sets the lower limit for PID output. The drive uses the largest value of b5-91, b5-34 [PID Output
Lower Limit], and d2-02 [Frequency Reference Lower Limit] to internally set the lower limit of PID output. The
b5-89 setting does not have an effect.
b5-92 [EZ Sleep Level] When the output frequency or motor speed is less than the value of b5-92 for longer than the value of b5-93 [EZ
Sleep Time], the drive does to sleep.
b5-95 = 0 [EZ Sleep Wake-up Mode = Absolute] When the PID feedback is less than the value of b5-94 [EZ Sleep Wake-up Level] for longer than the time set in
b5-96 [EZ Sleep Wake-up Time], the drive restarts operation from sleep.
b5-95 = 1 [EZ Sleep Wake-up Mode = Setpoint Delta] The drive resumes operation from the sleep state when the PID feedback has dropped below the value defined as
the PID setpoint value minus b5-94 continuously for the time configured with b5-96.
Figure 12.38 EZ Sleep/Wake-up Operation: PID Output is Normal and b5-92 = 0.0 Hz
*1 The values of b5-94 and b5-95 set operation.
*2 In the example, b5-92 is at the default setting of 0.0 Hz. Parameter b5-91 is the EZ sleep level.
■ b5-01: PID Mode Setting
No.
(Hex.)
Name Description
Default
(Range)
b5-01
(01A5)
PID Mode Setting
Sets the type of PID control.
0
(0 - 8)
0 : PID control disabled
1 : Standard
Enables PID control. The drive performs D control on the difference between the feedback value and the PID setpoint
output via U5-02 [PID Input].
2 : Standard (D on feedback)