EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.9 L: Protection Functions
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 969
Figure 12.128 KEB Function Wiring Example
Parameters for KEB Ride-Thru
Table 12.67 shows the parameters that adjust the KEB Ride-Thru function. Parameter settings are different for the
different KEB methods set in L2-29 [KEB Energy Backup Method].
Table 12.67 Parameters for KEB Ride-Thru
No. Name Configuring Settings
L2-29 [Kinetic Energy Backup Method]
0 1 2 3
C1-09 Fast Stop Time If ov [Overvoltage] occurs during KEB deceleration, increase the setting value.
If Uv1 [DC Bus Undervoltage] occurs during KEB deceleration, decrease the
setting value.
x
*1
- - -
C2-03 S-Curve Time @ Start of Decel If ov occurs immediately after you start KEB deceleration, increase the setting
value.
If Uv1 occurs immediately after you start operation, decrease the setting value.
x - x x
L2-05 Undervoltage Detection Lvl
(Uv1)
If Uv1 occurs immediately after you start KEB deceleration, increase the setting
value to detect power loss more quickly.
x x x x
L2-06 Kinetic Energy Backup Decel
Time
Does KEB Tuning.
If ov or Uv1 occur during KEB deceleration after the KEB Tuning, set L2-06 in
these conditions:
If ov occurs, increase the setting value
If Uv1 occurs, decrease the setting value.
- - x
*2
x
*2
L2-07 Kinetic Energy Backup Accel
Time
Sets the acceleration time to return to the frequency reference value before a power
loss, after you cancel the KEB operation. When L2-07 = 0, the drive uses the
standard acceleration times set in C1-01, C1-03, C1-05, and C1-07 [Acceleration
Time].
x x x x
L2-08 Frequency Gain at KEB Start If ov occurs immediately after you start operation, decrease the setting value.
If Uv1 occurs immediately after you start KEB deceleration, increase the setting
value.
x - x x
L2-10 Minimum KEB Time With KEB Ride-Thru
There is Uv1 because you set a digital input for KEB Ride-Thru and the device
that controls the input operated too slowly after power loss.
Without KEB Ride-Thru
If the DC bus voltage overshoots immediately after KEB Ride-Thru starts,
increase L2-10 to longer than the overshoot.
x x x x
L2-11 KEB DC Bus Voltage Setpoint Single Drive KEB Ride-Thru 2
Set to approximately 1.22 x input voltage.
Single Drive KEB Ride-Thru 1, System KEB Ride-Thru 1, or System KEB Ride-
Thru 2
Set to approximately 1.4 x input voltage.
x x x x
L3-20 DC Bus Voltage Adjustment
Gain
If ov or Uv1 occurs at the start of deceleration when you use KEB operation,
increase this value in 0.1-unit increments.
If there is torque ripple during deceleration when you use KEB Ride-Thru,
decrease the value.
- x - -