12.9 L: Protection Functions
982 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
L3-11 = 1 [Overvoltage Suppression Select = Enabled]
H1-xx = 7A or 7B [MFDI Function Selection = KEB Ride-Thru 2 Activate (N.O./N.C.)]
Note:
If stall prevention during deceleration function causes large speed or current ripples and L2-29 = 1, H1-xx = 7A or 7B, or L3-04 = 2,
gradually decrease this parameter in 0.05-unit increments. If the drive detects ov [Overvoltage] or oC [Overcurrent], decrease L3-21. If you
decrease the gain too much, it can cause a delay in control in the DC bus voltage or the deceleration time could be longer than the best
deceleration time.
If sudden increases in the regenerative load cause ov faults and L3-11 = 1, gradually increase this parameter in 0.1-unit increments. If there
are large speed ripples, gradually decrease this parameter in 0.05-unit increments.
L3-22: PM Stall Prevention Decel Time
No.
(Hex.)
Name Description
Default
(Range)
L3-22
(04F9)
PM Stall Prevention Decel
Time
Sets the momentary deceleration time that the drive will use when it tries to accelerate a PM motor
and detected motor stalls. This function is applicable when L3-01 = 1 [Stall Prevention during Accel
= Enabled].
0.0 s
(0.0 - 6000.0 s)
Set this parameter to 0.0 s to disable this function. The drive will decelerates in the deceleration time applicable at the
time when a motor stall occurs.
L3-23: Stall P Reduction at Constant HP
No.
(Hex.)
Name Description
Default
(Range)
L3-23
(04FD)
Stall P Reduction at
Constant HP
Sets the function to automatically decrease the Stall Prevention Level during Run for Constant Horse
Power (CHP) part of the speed range.
0
(0, 1)
0 : Use L3-06 for Entire Speed Range
The drive uses the level set in L3-06 [Stall Prevent Level during Run] through the full speed range.
1 : Automatic Reduction @ CHP Region
The drive decreases the Stall Prevention level during run in the constant power range. The lower limit is 40% of the
L3-06 value.
L3-24: Motor Accel Time @ Rated Torque
No.
(Hex.)
Name Description
Default
(Range)
L3-24
(046E)
Expert
Motor Accel Time @ Rated
Torque
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque for
stopped single-drive motors.
Determined by o2-04, C6-
01, E2-11, and E5-01
(0.001 - 10.000 s)
Set one of these parameters to enable L3-20:
L2-29 = 1 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2]
L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
L3-11 = 1 [Overvoltage Suppression Select = Enabled]
H1-xx = 7A or 7B [MFDI Function Selection = KEB Ride-Thru 2 Activate (N.O./N.C.)]
Note:
When Auto-Tuning changes the value of E2-11 [Motor Rated Power], the drive will automatically set L3-24 to the value for a Yaskawa
standard motor (4 poles). When you use a PM motor, the drive uses the value in E5-01 [PM Motor Code Selection] to change L3-24.
Automatically Adjust Parameters
When A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM], do Inertia Tuning. Parameters are automatically
adjusted.
Manually Adjust Parameters
Use this formula to find the motor acceleration time:
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV