12.9 L: Protection Functions
992 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
The drive will not detect overtorque or undertorque.
1 : oL @ Speed Agree - Alarm only
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not occur
during acceleration/deceleration. The drive outputs an oL3 [Overtorque Detection 1] and operation continues.
2 : oL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an oL3 and operation
continues.
3 : oL @ Speed Agree - Fault
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not occur
during acceleration/deceleration. The drive outputs an oL3 and operation stops.
4 : oL @ RUN - Fault
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an oL3 and operation
stops.
5 : UL @ Speed Agree - Alarm only
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL3 [Undertorque Detection 1] and operation continues.
6 : UL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a UL3 and operation
continues.
7 : UL @ Speed Agree - Fault
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL3 and operation stops.
8 : UL @ RUN - Fault
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a UL3 and operation
stops.
L6-02: Torque Detection Level 1
No.
(Hex.)
Name Description
Default
(Range)
L6-02
(04A2)
Torque Detection Level 1
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
Note:
Set the torque detection level as a percentage of the drive rated output current in all control methods to set the mechanical weakening
detection level.
You can also use an analog input terminal to supply the torque detection level. To enable this function, set H3-xx = 7 [MFAI Function Select
= Overtorque/Undertorque DetectLvl]. If you set L6-02 and H3-x = 7, the analog input is most important and the drive disables L6-02.
L6-03: Torque Detection Time 1
No.
(Hex.)
Name Description
Default
(Range)
L6-03
(04A3)
Torque Detection Time 1
Sets the detection time for Overtorque/Undertorque Detection 1.
0.1 s
(0.0 - 10.0 s)
L6-04: Torque Detection Selection 2
No.
(Hex.)
Name Description
Default
(Range)
L6-04
(04A4)
Torque Detection Selection 2
Sets the speed range that detects overtorque and undertorque and the operation of drives (operation
status) after detection.
0
(0 - 8)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV