Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.0 / real32(Visible when 14.1 Module 1 type = FAIO-01)
Defines the real value of the signal (selected by
parameter 14.87 AO2 source) that corresponds to the
minimum AO2 output value (defined by parameter 14.92
AO2 out at AO2 src min).
I
AO2
(mA)
Signal (real)
selected by par
14.87
14.93
14.92
14.90
14.91
I
AO2
(mA)
Signal (real)
selected by
14.87
14.93
14.92
14.91
14.90
AO2 source min14.90
1 = 1 / 10 = 1Real signal value corresponding to minimum AO2
output value.
-32768.0 ... 32767.0
100.0 / real32(Visible when 14.1 Module 1 type = FAIO-01)
Defines the real value of the signal (selected by
parameter 14.87 AO2 source) that corresponds to the
maximum AO2 output value (defined by parameter
14.93 AO2 out at AO2 src max). See parameter 14.90
AO2 source min.
AO2 source max14.91
1 = 1 / 10 = 1Real signal value corresponding to maximum AO2
output value.
-32768.0 ... 32767.0
0.000 mA / real32(Visible when 14.1 Module 1 type = FAIO-01)
Defines the minimum output value for analog output
AO2.
See also drawing at parameter 14.90 AO2 source min.
AO2 out at AO2 src
min
14.92
1000 = 1 mA / 1000 =
1 mA
Minimum AO2 output value.0.000 ... 20.000 mA