EasyManua.ls Logo

ABB ACS880 N5700 Series - Page 426

ABB ACS880 N5700 Series
662 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
None / uint32Parameters 61.5161.74 preselect data to be sent in
data sets 11, 13, 15, 17, 19, 21, 23 and 25 to the external
controller.
Parameters 61.10161.124 display the data to be sent
to the external controller. If no data has been
preselected, the value to be sent can be written directly
into these parameters.
For example, this parameter preselects the data for
word 1 of data set 11. Parameter 61.101 Data set 11 data
1 value displays the selected data in integer format. If
no data is preselected, the value to be sent can be
written directly into parameter 61.101.
Data set 11 data 1
selection
61.51
0None.None
1Control Word (16 bits)CW 16bit
4Status Word (16 bits)SW 16bit
5Actual value ACT1 (16 bits)Act1 16bit
6Actual value ACT2 (16 bits)Act2 16bit
See Terms and abbreviations (page 130).Other [value]
None / uint32Preselects the data to be sent as word 2 of data set 11
to the external controller.
See also parameter 61.102 Data set 11 data 2 value.
For the selections, see parameter 61.51 Data set 11 data
1 selection.
Data set 11 data 2
selection
61.52
None / uint32Preselects the data to be sent as word 3 of data set 11
to the external controller.
See also parameter 61.103 Data set 11 data 3 value.
For the selections, see parameter 61.51 Data set 11 data
1 selection.
Data set 11 data 3
selection
61.53
None / uint32See parameter 61.51 Data set 11 data 1 selection.Data set 13 data 1
selection
61.54
None / uint32See parameter 61.51 Data set 11 data 1 selection.Data set 25 data 3
selection
61.74
0 / uint16Displays (in integer format) the data to be sent to the
external controller as word 1 of data set 2.
If no data has been preselected by 61.45 Data set 2 data
1 selection, the value to be sent can be written directly
into this parameter.
Data set 2 data 1
value
61.95
- / -Data to be sent as word 1 of data set 2.0...65535
0 / uint16Displays (in integer format) the data to be sent to the
external controller as word 2 of data set 2.
If no data has been preselected by 61.46 Data set 2 data
2 selection, the value to be sent can be written directly
into this parameter.
Data set 2 data 2
value
61.96
- / -Data to be sent as word 2 of data set 2.0...65535
426 Parameters

Table of Contents