Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 = Nm (N·m)
1 = lbft (lbf·ft)
Torque unitb4
Reservedb5…15
1 = 10000h…FFFFh
DDCS Controller /
uint16
Defines the 1st priority external source for
synchronization of the drive's time and date.
The date and time can also be directly set into
96.24 … 96.26 in which case this parameter is ignored.
Time sync primary
source
96.20
0No external source selected.Internal
1External controller.DDCS Controller
2Fieldbus interface A or B.Fieldbus A or B
3Fieldbus interface A.Fieldbus A
4Fieldbus interface B.Fieldbus B
5The master station on a master/follower or
drive-to-drive link.
D2D or M/F
6Embedded fieldbus interface.Embedded FB
8Control panel, or Drive Composer PC tool connected
to the control panel.
Panel link
9Drive Composer PC tool through an FENA module.Ethernet tool link
Inactive / uint16In the master drive, activates clock synchronization for
master/follower and drive-to-drive communication.
M/F and D2D clock
synchronization
96.23
0Clock synchronization not active.Inactive
1Clock synchronization active.Active
- / uint16Number of full days passed since beginning of the year
1980. This parameter, together with 96.25 Time in
minutes within 24 h and 96.26 Time in ms within one
minute makes it possible to set the date and time in
the drive via the parameter interface from a fieldbus
or application program. This may be necessary if the
fieldbus protocol does not support time
synchronization.
Full days since 1st
Jan 1980
96.24
1 = 1 days / 1 = 1 daysDays count. 1 = 1st January 1980.1...59999 days
0 min / uint16Number of full minutes passed since midnight. For
example, the value 860 corresponds to 2:20 pm.
See parameter 96.24 Full days since 1st Jan 1980.
Time in minutes
within 24 h
96.25
1 = 1 min / 1 = 1 minMinutes since midnight.0...1439 min
0 ms / uint16Number of milliseconds passed since last minute.
See parameter 96.24 Full days since 1st Jan 1980.
Time in ms within
one minute
96.26
1 = 1 ms / 1 = 1 msNumber of milliseconds since last minute.0...59999 ms
- / uint16Time source status word.
Note: This parameter is read-only.
Time sync source
status
96.29
1 = 1st priority tick received: Tick has been received
from 1st priority source (or from 96.24 … 96.26).
Time tick receivedb0
Parameters 521