Bit Name Val. Information
0 START ACT 1 Drive start command is active.
0 Drive start command is inactive.
1 STOP ACT 1 Drive stop command is active.
0 Drive stop command is inactive.
2 READY RELAY 1 Ready to function: run enable signal on, no fault, emergency stop
signal off, no motor ID run inhibition. Connected by default to DIO1
by par. 12.04 DIO1 OUT PTR. (Can be freely connected anywhere.)
0 Not ready to function
3 MODULATING 1 Modulating: IGBTs are controlled, ie, the drive is RUNNING.
0 No modulation: IGBTs are not controlled.
4 REF RUNNING 1 Normal operation is enabled. Running. Drive follows the given
reference.
0 Normal operation is disabled, Drive is not following the given
reference (eg, in magnetisation phase drive is modulating).
5 JOGGING 1 Jogging function 1 or 2 is active.
0 Jogging function is inactive.
6 OFF1 1 Emergency stop OFF1 is active.
0 Emergency stop OFF1 is inactive.
7 START INH
MASK
1 Maskable (by par. 10.12 START INHIBIT) start inhibit is active.
0 No start inhibit (maskable)
8 START INH
NOMASK
1 Non-maskable start inhibit is active.
0 No start inhibit (non-maskable)
9CHRG REL
CLOSED
1 Charging relay is closed.
0 Charging relay is open.
10 STO ACT 1 Safe Torque Off function is active. See parameter 46.07 STO DIAG-
NOSTIC.
0 Safe Torque Off function is inactive.
11 Reserved
12 RAMP IN 0 1 Ramp Function Generator input is forced to zero.
0 Normal operation
13 RAMP HOLD 1 Ramp Function Generator output is held.
0 Normal operation
14 RAMP OUT 0 1 Ramp Function Generator output is forced to zero.
0 Normal operation
15 DATA LOGGER
ON
1 The drive data logger is on and has not been triggered.
0 The drive data logger is off, or its post-trigger time has not yet
elapsed. See the DriveStudio user manual.