Parameters and firmware blocks
123
(6) IN1S IN2DIR The source selected by 10.05 EXT2 START IN1 is the start signal
(0 = stop, 1 = start), the source selected by 10.06 EXT2 START IN2 is
the direction signal (0 = forward, 1 = reverse).
10.05 EXT2 START IN1 FW block: DRIVE LOGIC (see above)
Selects the source 1 for the start and stop commands in external control location EXT2. See
parameter 10.04 EXT2 START FUNC selections (1) In1 and (2) 3-wire.
Note: This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.06 EXT2 START IN2 FW block: DRIVE LOGIC (see above)
Selects the source 2 for the start and stop commands in external control location EXT2. See
parameter 10.04 EXT2 START FUNC selection (2) 3-wire.
Note: This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.07 JOG1 START FW block: DRIVE LOGIC (see above)
If enabled by parameter 10.15 JOG ENABLE, selects the source for the activation of jogging function
1. 1 = Active. (Jogging function 1 can also be activated through fieldbus regardless of parameter
10.15.)
See section Jogging on page 50. See also other jogging function parameters: 10.14 JOG2 START,
10.15 JOG ENABLE, 24.03 SPEED REF1 IN / 24.04 SPEED REF2 IN, 24.10 SPEED REF JOG1,
24.11 SPEED REF JOG2, 25.09 ACC TIME JOGGING, 25.10 DEC TIME JOGGING and 22.06 ZERO
SPEED DELAY.
Note: This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.08 FAULT RESET SEL FW block: DRIVE LOGIC (see above)
Selects the source for the external fault reset signal. The signal resets the drive after a fault trip if the
cause of the fault no longer exists. 1 = Fault reset.
Bit pointer: Group, index and bit
10.09 RUN ENABLE FW block: DRIVE LOGIC (see above)
Selects the source for the run enable signal. If the run enable signal is switched off, the drive will not
start or stops if the drive is running. 1 = Run enable.
See also parameter 10.17 START ENABLE.
Note: This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.10 EM STOP OFF3 FW block: DRIVE LOGIC (see above)
Selects the source for the emergency stop OFF3. 0 = OFF3 active: The drive is stopped along the
emergency stop ramp time, 25.11 EM STOP TIME.
Emergency stop can also be activated through fieldbus (2.12 FBA MAIN CW).
See section Emergency stop on page 82.
Note: This parameter cannot be changed while the drive is running.